裝置端異常偵測:統計基線與學習模型比較
On-Device Anomaly Detection: Statistical Baselines vs. Learned Models
文章比較裝置端異常偵測的統計基線與學習模型,按點離羣值、水平漂移、訊號形狀變化及通道相關性説明各自適用情況。作者提供以 EWMA、MAD 和遲滯機制組成的統計基線程式,並以 180 台泵的數據比較偵測時間、每日誤報及警報精確率。文章建議以基線作為篩選與後備,只對觸發的視窗執行模型;在 200 台裝置的羣組中,推理 CPU 用量約減少 90%,偵測延遲維持不變。
There is a reflex in IoT projects that goes: "we have anomaly data, so we need a model." Often the honest answer is that a robust statistical baseline will detect 80% of the incidents with 2% of the engineering effort — and, crucially, with far fewer false alarms during the first two weeks after commissioning, which is exactly when trust is built.
This post compares the two approaches honestly, gives you working code for the statistical side, and describes the hybrid that I end up shipping most of the time.
What "anomaly" means operationally
Before comparing detectors, define what you are detecting. Three very different problems get called "anomaly detection":
- Point outliers — a single sample outside the historical range. Sensor glitch, transient spike.
- Level shift / drift — the process moves to a new operating point and stays there. Fouling, wear, a changed setpoint.
- Shape change — the signal's dynamics change while its mean stays flat. Bearing defect, looseness, cavitation.
A robust z-score handles (1) well and (2) adequately. It is poor at (3), because crest factor and spectral content can change dramatically with an unchanged mean. If your failure modes are mostly (3), a model that sees a window of raw or lightly processed samples earns its complexity. If they are (1) and (2), a statistical baseline is not a compromise — it is the right tool.
The baseline, properly done
A naive mean ± 3σ fails for three reasons: spikes inflate σ, the distribution is rarely Gaussian, and it ignores time. Fix all three:
import numpy as np
class RobustBaseline:
"""Median/MAD baseline with EWMA smoothing and hysteresis.
Handles spikes (median), non-Gaussian tails (MAD + quantile),
and slow drift (EWMA) without a training pipeline.
"""
MAD_TO_SIGMA = 1.4826
def __init__(self, alpha=0.02, warmup=300, k_warn=4.0, k_alarm=6.0, hold=5):
self.alpha = alpha
self.warmup = warmup
self.k_warn = k_warn
self.k_alarm = k_alarm
self.hold = hold
self.n = 0
self.med = None
self.mad = None
self.state = "ok"
self._over = 0
def update(self, x: float) -> tuple[str, float]:
if self.med is None:
self.med, self.mad = x, 1e-6
self.n += 1
# EWMA on centre and spread: adapts to setpoint changes, resists spikes
self.med += self.alpha * (x - self.med)
self.mad += self.alpha * (abs(x - self.med) - self.mad)
sigma = max(self.mad * self.MAD_TO_SIGMA, 1e-9)
z = (x - self.med) / sigma
# during warm-up, only widen the band; never alert
if self.n < self.warmup:
return "warmup", z
if abs(z) >= self.k_alarm:
self._over += 1
else:
self._over = 0
if self._over >= self.hold:
self.state = "alarm"
elif abs(z) >= self.k_warn:
self.state = "warn"
elif self.state == "alarm" and abs(z) < self.k_warn:
self.state = "warn"
elif abs(z) < self.k_warn * 0.5:
self.state = "ok"
return self.state, z
Four design choices carry most of the value:
- EWMA rather than a fixed historical window. A machine that ramps to a new load for 20 minutes is not anomalous; a fixed baseline from last month says it is. The EWMA follows the operating point.
- MAD rather than σ. One 10× spike changes σ by a lot and median absolute deviation by almost nothing.
- A warm-up period that never alerts. You will thank yourself on day one of every deployment.
-
Hold-down plus hysteresis (
k_alarm>k_warn, and a return threshold at half ofk_warn). This alone typically cuts alert volume by half. More on that in the hysteresis post.
Where the baseline breaks
Three failure modes are worth knowing because they tell you when to graduate to a model:
Correlated channels. A temperature rise in a motor is normal if current also rose and the ambient did not. A per-channel z-score cannot express "high, but consistent with load". This is where a learned model — or even a simple multivariate Mahalanobis distance — wins immediately.
Shape-only faults. A crest-factor rise from 2.1 to 3.4 on a bearing is a classic early indicator that stays invisible to a mean-based detector. If your maintenance history is dominated by these, you need window features or a model.
Multi-modal normal behaviour. A compressor that runs loaded, idle, and in a defrost cycle has three distinct "normal" operating points. A single centre/spread pair produces alerts at every transition. You can fix this with mode-conditioned baselines (one RobustBaseline per mode) — which is usually the cheap correct answer, and a strong argument against reaching for a neural network too early.
Fair comparison: the metrics that matter
Do not compare detectors with AUC. Compare them the way operations experiences them:
- Time to detect — minutes from fault onset to first alarm, per incident.
- False alarms per device per day — the number your on-call rotation actually feels.
- Alert precision — share of alarms a technician judges actionable.
- Lead time before failure — for predictive maintenance, the window in which you can act.
A worked comparison table from a real fleet of 180 pumps looked like this:
| Detector | Median time to detect | False alarms / device / day | Precision | Flash need |
|---|---|---|---|---|
| Per-channel robust z | 41 min | 1.8 | 0.34 | < 1 KB |
| Multivariate Mahalanobis | 22 min | 0.9 | 0.52 | ~ 2 KB |
| 1D CNN on raw window | 8 min | 0.4 | 0.71 | 96 KB |
| CNN + rule engine + dedup | 8 min | 0.1 | 0.88 | 96 KB |
Note the last row: the big win in precision did not come from a better model, it came from the rule engine and de-duplication layered on top. That pattern repeats — the model is rarely the whole answer.
The Mahalanobis row is worth dwelling on. It costs a covariance matrix and a few multiplications, fits in a couple of kilobytes, and captures load-correlated behaviour that per-channel z-scores miss. For many fleets it is the best effort-to-value ratio available.
import numpy as np
class MahalanobisBaseline:
def __init__(self, feature_names, shrink=0.10):
self.names = feature_names
self.shrink = shrink
self.mu = None
self.inv_cov = None
def fit(self, X: np.ndarray) -> "MahalanobisBaseline":
self.mu = X.mean(axis=0)
cov = np.cov(X, rowvar=False)
# shrinkage keeps the inverse stable with correlated features
cov = (1 - self.shrink) * cov + self.shrink * np.eye(cov.shape[0]) * np.trace(cov) / cov.shape[0]
self.inv_cov = np.linalg.inv(cov)
return self
def score(self, x: np.ndarray) -> float:
d = x - self.mu
return float(np.sqrt(d @ self.inv_cov @ d))
Score thresholds come from the chi-square distribution, not from a 3σ rule: for d features, the 99.9th percentile of χ²(d) is a defensible alarm threshold. Hardcode the resulting constant in the firmware so the device does not need a stats library.
The hybrid I usually ship
per-sample → device: hard limits (deterministic, no model)
per-window → gateway: robust baseline per operating mode (cheap, always on)
└─ if |z| > k_warn: run the learned model on the window
per-event → cloud: correlation, dedup, triage
The baseline acts as a cheap gate, and the model runs only on windows the baseline flagged. On a 200-device fleet this cut inference CPU by roughly 90% while keeping detection latency identical, because the baseline catches the same onsets the model does — it just cannot say much about what is happening.
There is a second benefit that matters more: the baseline is the fallback. If a model update goes wrong, or a device's model fails to load, the baseline still detects level shifts and point outliers. A pipeline whose only detector is a neural network has no degraded mode; it has an outage.
Guarding the baseline against setpoint changes
Baselines go bad when the process changes: a new product run, a retuned controller, a replaced sensor. Three cheap guards:
1 Mode-conditioned state. Key the baseline on an operating mode supplied by the machine, not inferred. baselines[mode].update(x).
2 Commissioning reset with an explicit window. Allow a supervised "rebaseline" that ignores data for N minutes after a setpoint command, so the ramp itself never becomes the new normal.
3 Slow-drift detection on the baseline itself. Track med over days; if it moves more than X% without a maintenance event, that is a signal in its own right, not noise to be absorbed.
That third guard is genuinely useful. On one fleet, the alarm that actually predicted failures was not a z-score at all — it was "the EWMA centre of the vibration RMS moved 15% in a week without a setpoint change". Slow, boring, and more predictive than the model.
Deciding
Use the baseline alone when: your failure modes are point outliers or level shifts, you have fewer than ~10 correlated channels, and your false-alarm budget is tight from day one.
Add a learned model when: faults are shape-based, channels are strongly correlated, or you have enough labelled incidents to evaluate a model honestly (a dozen is not enough to distinguish a model from a baseline — you need dozens).
Ship the hybrid almost always: baseline as gate and fallback, model for diagnosis, rule engine and de-duplication on top. That is the architecture the rest of this series builds toward.
Next: Designing a Rule Engine That Complements Your ML Model.
來源:DEV Community · dev.to